Page 7-22 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Coolant Heat Exchanger Removal/Installation (Cont) Refill engine coolant as required Refer to Drain and Flush Coolant System in Section 5. Install the coolant system pressure cap (Cummins Fire Power Part No. 11407). Reconnect the coolant heater power supply. For safety reasons, both batteries must be re- connected before putting the engine and fire protection system controller back in service. Wear safety glasses when reconnecting batteries! Reconnect the batteries at their terminals after all service work has been completed. NOTE : Start the engine and do a quick check for leaks.
If any coolant leaks are observed, stop the engine, repair the leak, check coolant level, then restart the engine. If no leaks are present, promptly establish raw water flow through the heat exchanger. Start the engine. Refer to Normal Local Starting Procedure in Section 3. Check for and repair any coolant leaks. Drawing No. 9777, Section 7, Rev. 02-07