Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7– Adjustment, Repair, and Replacement Page 7-69 CFP83 Series Alternator Checks and Testing (Cont) Alternator Amperage Output Test NOTE : Conduct this testing at normal shop temperature. NOTE : Refer to Electrical Specifications in Section 10 for the minimum required alternator output. Use the value listed for the system voltage. Connect a carbon pile load in parallel across the battery terminals. Refer to Jumpering the Batteries in Section 3 for how to make a parallel connection. Connect a clamp-on (induction) ammeter across the alternator output cable. Start the engine and operate at rated speed. Refer to Normal Local Starting Procedure in Section 3.

Adjust the carbon pile for maximum indication. Note the amperage indicated on the ammeter. Stop the engine. Remove the test equipment. Replace the alternator if the output is not 90% or more of the specification value. Refer to Alternator Removal/Installation in this section. Drawing No. 9777, Section 7, 02-07