Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 7-68 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Alternator Checks and Testing (Cont) Alternator Voltage Output Test CAUTION Batteries must have been satisfactorily load tested and must be charged with a resting voltage of more than 12.4 Volts for this testing. CAUTION Batteries must have been satisfactorily load tested and must be charged with a resting voltage of more than 12.4 Volts for this testing. NOTE : Conduct this testing at normal shop temperature. NOTE : Voltage should not exceed 15.5 V (for a 12 VDC system) or 31 V (for a 24 VDC system). Start the engine and operate at rated speed. Refer to Normal Local Starting Procedure in Section 3.

Measure the alternator voltage output to the batteries with digital multimeter, Cummins Part Number 3377161. Stop the engine. Replace the alternator if the voltage exceeds specification. Refer to Alternator Removal/Installation in this section. Drawing No. 9777, Section 7, Rev. 02-07