Section 7 – Adjustment, Repair, and Replacement Page 7-99 CFP83 Series Exhaust Restriction Measurement Measure NOTE : The maximum acceptable exhaust restriction is listed in Exhaust System Specifications in Section 10. NOTE : A new pressure tap in the customer- supplied exhaust piping may be required. Install pressure gauge, Cummins Part Number ST-1273, in the exhaust piping at the connection to the fire pump. Operate the engine at rated speed and load. Refer to Normal Local Starting Procedure in Section 3. Observe the exhaust restriction. Stop the engine. Refer to Normal Local Starting Procedure in Section 3. Remove the pressure gauge and plug the pressure tap.
If the backpressure exceeds specification, modify the exhaust piping accordingly. Drawing No. 9777, Section 7, Rev. 02-07