Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 7-130 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Measure Fuel Drain Line Restriction Refer to Fuel Drain Line Restriction (41-006-012) in C Series Troubleshooting and Repair Manual, Bulletin No. 3666003. Measure Remove the fuel drain line from the fitting at the injection pump. Install the 0 to 207 kPa [0 to 30 psi] pressure gauge. Operate the engine at rated speed and no load. Observe the reading on the pressure gauge. Maximum Fuel Drain Line Restriction: 69 kPa [10 psi] If the drain line pressure is out of specification, check for bends or kinks in the drain lines. Drawing No. 9777, Section 7, Rev. 02-07