Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-129 CFP83 Series Air in Fuel (Cont) If bubbles are present, check for air leaks in the fuel supply circuit. Measure the amount of fuel in the container. If more than 1.33 liters [45 fl oz] are collected and the fuel is bubble-free, then it is unlikely the low- pressure fuel system is the cause of engine operational problems. Reconnect the lift pump that is retaining the fuel filter pressure connections. Running engine at high idle, the filter inlet pressure should be greater than 42.3 kPa [6 psi]; otherwise, there is a fuel lift pump malfunction.

If the fuel transfer pump does not run, check electrical circuits, and verify voltage is present at lift pump connector. NOTE : When an engine is not running, with switch on, the lift pump will run less than 2 seconds (varies with ECM calibration); with starter bump, about 25 to 30 seconds. If voltage is present, replace fuel transfer pump. Resistance measurement across the transfer pump terminals can be made for confirmation of pump malfunction. Resistance greater than 200 ohms or less than 0.2 ohm does confirm an electrical fault when voltage is present but the fuel pump is not running. Drawing No. 9777, Section 7, Rev. 02-07