Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-153 CFP83 Series Air Intake Restriction Indicator Removal/Installation Follow-Up Run engine to determine if new indicator is functioning. Drawing No. 9777, Section 7, Rev. 02-07 A mechanical restriction indicator is available to indicate excessive air restriction through a dry- type air cleaner. This instrument is mounted on the air cleaner outlet tube. Refer to Air Filter Assembly Drawing in Section 13. Change the filter element when the red indicator flag (2) is at the raised position in the window (1). See Air Cleaner Element Removal/Installation this section. NOTE: Do not remove the felt washer from the indicator.

The felt washer absorbs moisture. After the air cleaner has been serviced, push the button (3) to reset the service indicator. If the indicator does not retract to the service position with new air cleaner element installed, the service indicator needs to be replaced. Remove service indicator from Air Cleaner Element piping. Apply Teflon sealant to the threads on the indicator. Install new indicator on Intake pipe.