Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 7-188 Section 7 – Adjustment, Repair, and Replacement CFP83 Series Lubricating Oil Cooler Removal/Installation (Cont) Fill CAUTION The system must be filled slowly to prevent air locks. Be sure to open the aftercooler to allow air to escape as the system is filled. Fill the coolant system and lubricating oil system. Operate the engine to check for leaks. Stop the engine and check the coolant and oil level. Pressure Test Pressurize the element to 690 kPa [100 psi] to check it for leaks. Follow-Up Drawing No. 9777, Section 7, Rev. 02-07