Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-203 CFP83 Series Lubricating Oil Pump Removal/Installation (Cont) Install the vibration damper. Refer to Procedure 001-051 or Procedure 001-052. Tighten the vibration damper. Refer to Procedure 001-051 or Procedure 001-052. Torque Value: 125 N•m [92 ft-lb] Raise the belt tensioner to install the belt. Refer to Procedure 008-002. Follow-Up Drawing No. 9777, Section 7, Rev. 02-07