Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-25 CFP83 Series Auto Start Failure – Engine Starts but Crank Terminate does not Occur Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction The overspeed switch not correctly adjusted or has failed. When practical, with the engine running, verify speed sensor input to the overspeed switch. Refer to Drawing 10423 Sheet 1 in Section 13. If signal is not present, go to The speed sensor has failed. The tachometer also indicates zero speed in this table. Adjust the overspeed switch crank terminate setpoint. Refer to instructions in Section 3. If required, replace the overspeed switch. Refer to Overspeed Switch Removal/Installation in Section 7.

Fuse 3 has opened. The raw water solenoid valve also fails to open. Open the raw water bypass valves. When practical, replace Fuse F3. Locate and repair any local electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. The speed sensor has failed. The tachometer also indicates zero speed. When practical, locate and repair any electrical fault in the speed sensor circuitry. Refer to Drawing 10423 Sheet 1 in Section 13. If necessary, replace the speed sensor. Refer to Speed Sensor Removal/Installation in Section 7. An electrical fault is present in the Fire Protection System.

When practical, test continuity and insulation from ground in the fire protection system and the engine control panel. Locate and repair any electrical fault in the fire protection system panel. An electrical fault is present between Control Panel TB 2 and the Fire Protection System. When practical, test continuity and insulation from ground between the fire protection system and the engine control panel. Locate and repair any electrical fault in the field wiring.