Page 12-24 Section 12 – Troubleshooting CFP83 Series Auto Start Failure – Cranks but does not Start (Cont) Drawing No. 9777, Section 12, Rev. 02-07 The overspeed switch has failed. Check power and grounding to the overspeed switch. Refer to Drawing 10423 Sheet 1 in Section 13. Repair any electrical faults. If required, test and adjust the overspeed setting. Refer to Overspeed Setpoint Adjustment and Testing in Section 3. Replace the overspeed switch. Refer to Overspeed Switch Removal/Installation in Section 7. Contact an Authorized Cummins Repair Facility.