Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-23 CFP83 Series Auto Start Failure – Cranks but does not Start NOTE: The fire pump engine will crank automatically when either solenoid A or solenoid B is selected at the fire protection system. However, the engine does not start. The engine will start locally. If local starting problems are identified, go to the applicable Manual Start Failure troubleshooting table. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction The overspeed switch as actuated. The overspeed lamp is illuminated on the local control panel. Press the RESET switch on the local control panel.

Control power from the Fire Protection System is not available at local control panel TB1. When practical, locate and correct the fault in the Fire Protection System or the field wiring to the local control panel. Circuit Breaker CB is open in the local control panel. Check whether Circuit Breaker CB at the local control panel is open. Refer to Drawing 10423 Sheet 1 in Section 13. If open, reset the circuit breaker. Locate and correct any electrical faults in the control panel. Press the RESET switch on the local control panel. The AUTO/MANUAL Rocker Switch fails to select AUTO mode. When practical, open Circuit Breaker CB at the local control panel and test switch operation electrically.

Refer to Drawing 10423 Sheet 1 in Section 13. If required, replace the switch or repair other electrical faults. When done, close Circuit Breaker CB at the local control panel and reset rocker switch to Auto mode.