Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 12-22 Section 12 – Troubleshooting CFP83 Series Auto Start Failure - Does not Crank on A or B NOTE: The fire pump engine will not crank automatically when either solenoid A or solenoid B is selected at the fire protection system. However, it does crank and start when started locally. If local starting problems are identified, go to the applicable Manual Start Failure troubleshooting table. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction The Fire Protection System fails to produce either redundant start signal to the fire pump. Locate and correct the common mode fault in the Fire Protection System.