Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-21 CFP83 Series Auto Start Failure - Does not Crank on B NOTE: The fire pump engine will not crank automatically when solenoid B is selected at the fire protection system. However, it does start automatically when solenoid A is selected. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction The electrical connection from the fire protection system to Terminal Board TB 10 has failed. Test continuity and insulation from ground between the fire protection system and the engine control panel. Locate and repair any electrical fault in the field wiring or in the fire protection system panel.

The electrical connection from Terminal Board TB 10 to Relay K2 has failed. Test continuity and insulation from ground between the TB 10 and Relay K2. Locate and repair any electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. Relay K2 has failed. Check de-energized continuity at Relay K2 pin 87 to 30. Replace K1 if the circuit is open. Contact an Authorized Cummins Repair Facility.