Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 12-20 Section 12 – Troubleshooting CFP83 Series Auto Start Failure - Does not Crank on A NOTE: The fire pump engine will not crank automatically when solenoid A is selected at the fire protection system. However, it does start automatically when solenoid B is selected. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction The electrical connection from the fire protection system to Terminal Board TB 9 has failed. Test continuity and insulation from ground between the fire protection system and the engine control panel. Locate and repair any electrical fault in the field wiring or in the fire protection system panel.

The electrical connection from Terminal Board TB 9 to Relay K1 has failed. Test continuity and insulation from ground between the TB 9 and Relay K1. Locate and repair any electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. Relay K1 has failed. Check de-energized continuity at Relay K1 pin 87 to 30. Replace K1 if the circuit is open. Contact an Authorized Cummins Repair Facility.