Section 12 – Troubleshooting Page 12-19 CFP83 Series Raw Water Solenoid Valve Fails to Operate NOTE: The raw water solenoid failure may fail to open or to close. The normally closed valve may fail to open when the engine starts. This fault will prevent raw water flow through the normal valves. Bypass flow should be aligned in this event. The valve may also fail to close because of mechanical blockage. In this event, the raw water flow from the heat exchanger does not stop when it should. Depending upon the fire protection system piping, the open solenoid valve may drain all water from the fire protection system piping that is higher than the engine’s piping. Drawing No.
9777, Section 12, Rev. 02-07 Cause Correction Solenoid valve fails to close when the engine stops. Replace the solenoid valve. Refer to Raw Water Solenoid Valve Removal/Installation in Section 7. Clean the raw water strainer more frequently. Increase the frequency of operational testing. Solenoid valve fails to energize. Check electrical continuity and insulation from ground to the solenoid. Repair any open or short circuits in the wiring. Solenoid fails to open mechanically. NOTE: Apply the correct operating voltage, 12 VDC standard (24 VDC optional) depending upon the model. Apply temporary voltage to the solenoid. If the solenoid fails to operate, replace it.
Refer to Raw Water Solenoid Valve Removal/Installation in Section 7. Contact an Authorized Cummins Repair Facility.