Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 12-28 Section 12 – Troubleshooting CFP83 Series Manual Start Failure from Solenoid Lever - Does not Crank on B NOTE: The fire pump engine will not crank locally from the solenoid lever when solenoid B is actuated. However, it does start when solenoid A is actuated. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction Battery B is discharged or has failed. Recharge or replace the battery. An electrical fault is present between Battery B and the starter motor. When practical, test continuity and insulation from ground between Battery B and the starter motor. Locate and repair any electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13.

Solenoid B’s switch contact does not close. Remove and test Solenoid B lever and switch operation. Refer to Crank Solenoid Assembly Removal/Installation in Section 7. If required, replace Solenoid B. Contact an Authorized Cummins Repair Facility.