Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-29 CFP83 Series Manual Start Failure from Solenoid Lever - Does not Crank on A or B NOTE: The fire pump engine will not crank locally when either solenoid lever is actuated. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction Starter motor has failed. Replace the starter motor. Refer to Starter Motor Removal/Installation in Section 7. An electrical fault is present in the power or ground circuit for the starter motor. Test continuity and insulation from ground between the battery splice, the ground connection, and the starter motor. Locate and repair any electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. Engine is seized.

Bar the engine over to break the seizure. Contact an Authorized Cummins Repair Facility.