Page 12-30 Section 12 – Troubleshooting CFP83 Series Manual Start Failure from Control Panel - Does not Crank on A NOTE: The fire pump engine will not crank locally from the control panel when CRANK BATT A is selected. However, it does start when CRANK BATT B is selected. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction The CRANK BATT A switch fails to make contact. When practical, test the electrical operation of the CRANK BATT A switch. Refer to Drawing 10423 Sheet 1 in Section 13. Replace the switch if faulted. Relay K1 fails in the local manual mode. When practical, test the electrical operation of the Relay K1. Refer to Drawing 10423 Sheet 1 in Section 13.
Replace the relay if faulted. Solenoid A fails to energize due to electrical fault in the power or ground circuit. Test continuity and insulation from ground between the CRANK BATT A switch, Relay K1, and the starter Solenoid. Also, check the solenoid coil connection to ground. Locate and repair any electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. Solenoid A fails to operate. When practical, test the electrical operation of the Solenoid A. Refer to Drawing 10423 Sheet 1 in Section 13. Replace the solenoid if faulted. Contact an Authorized Cummins Repair Facility.