Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-31 CFP83 Series Manual Start Failure from Control Panel - Does not Crank on B NOTE: The fire pump engine will not crank locally from the control panel when CRANK BATT B is selected. However, it does start when CRANK BATT A is selected. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction The CRANK BATT B switch fails to make contact. When practical, test the electrical operation of the CRANK BATT B switch. Refer to Drawing 10423 Sheet 1 in Section 13. Replace the switch if faulted. Relay K2 fails in the local manual mode. When practical, test the electrical operation of the Relay K2. Refer to Drawing 10423 Sheet 1 in Section 13.

Replace the relay if faulted. Solenoid B fails to energize due to electrical fault in the power or ground circuit. Test continuity and insulation from ground between the CRANK BATT B switch, Relay K2, and the starter Solenoid. Also, check the solenoid coil connection to ground. Locate and repair any electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. Solenoid B fails to operate. When practical, test the electrical operation of the Solenoid B. Refer to Drawing 10423 Sheet 1 in Section 13. Replace the solenoid if faulted. Contact an Authorized Cummins Repair Facility.