Page 12-32 Section 12 – Troubleshooting CFP83 Series Manual Start Failure from Control Panel - Does not Crank on A or B NOTE: The fire pump engine will not crank locally from the control panel when either CRANK BATT A or CRANK BATT B is selected. However, it does start when a solenoid lever is actuated. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction The MANUAL mode rocker switch contact fails to close. When practical, test the electrical operation of the AUTO/MANUAL rocker switch. Refer to Drawing 10423 Sheet 1 in Section 13. Replace the solenoid if faulted. An electrical fault exists in the signal power circuit or the ground to the Relays K1 and K2.

Test continuity and insulation from ground between the AUTO/MANUAL rocker switch and the relays. Also, check the relay connection to ground. Locate and repair any electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. Fuse F3 has opened. The raw water solenoid valve also fails to open. Open the raw water bypass valves. When practical, replace Fuse F3. Locate and repair any local electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. An electrical fault exists in the signal power circuit or the ground to the overspeed switch’s crank circuit. Test continuity and insulation from ground between Fuse F3 and the overspeed switch’s crank circuit.

Also, check the crank circuit output to the CRANK BATT switches. Locate and repair any electrical fault. Refer to Drawing 10423 Sheet 1 in Section 13. Overspeed switch crank circuit fails to reset with engine shutdown. If required, test and adjust the crank setting. Refer to Overspeed Setpoint Adjustment and Testing in Section 3. If required, replace the overspeed switch. Refer to Overspeed Switch Removal/Installation in Section 7. Contact an Authorized Cummins Repair Facility.