Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-35 CFP83 Series Engine Cranks Normally But Will Not Start (No Exhaust Smoke) (Cont) Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction Fuel injection pump not getting fuel or air in fuel. Check fuel flow or bleed fuel system. Refer to Air in Fuel (006-003) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02. Fuel return restriction excessive. Inspect the fuel return lines for restrictions. Refer to Fuel Drain Line Restriction (006-012) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02. Fuel pump return overflow valve is malfunctioning. Inspect the return overflow valve.

Replace if necessary. Refer to Fuel Return Overflow Valve (006- 044) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02. Fuel injection pump timing is not correct. Put the engine at top dead center. Check and adjust the fuel timing. Refer to Fuel Injection Pumps, In-Line (005-012) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02. Injection pump driveshaft or driveshaft key is damaged. Repair or replace the injection pump. Refer to Fuel Injection Pump Removal/Installation in Section 7. Fuel injection pump is malfunctioning. Remove the fuel injection pump. Refer to Fuel Injection Pump Removal/Installation in Section 7.

Check the calibration of the fuel injection pump. Refer to Fuel Injection Pumps, In-Line (005-012) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02.