Section 12 – Troubleshooting Page 12-65 CFP83 Series Engine Stops During Operation Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction Normal automatic mode shutdown occurs when the fire protection systems removes the signal power feed to the local control panel. No action required This is a desirable outcome. In the automatic mode, the signal power feed is lost from the fire protection system to the control panel. Locate and correct the electrical fault in the fire protection system or the field wiring to the engine control panel. Signal power is lost by the operation of the circuit breaker the engine control panel. Press the circuit breaker reset button on the engine control panel.
Locate and correct the electrical fault in engine control panel. Refer to Drawing 10423 Sheet 1 in Section 13. An overspeed trip has occurred. The overspeed trip light is illuminated on the local control panel. Remote indications may also be present. Alternatively, a related overspeed switch failure has occurred. The trip indications may not be present. Go to Engine Overspeed Trip in this section. The fuel shutoff valve (FSOV) has failed. Check the wiring continuity and insulation from ground for the Fuel Shutoff Switch. Refer to Drawing 10423 Sheet 1 and Drawing 10423 Sheet 2 in Section 13. Correct any electrical faults. If required, replace the FSOV.
Refer to Fuel Shutoff Valve (FSOV) Removal/Installation in Section 7. Fuel tank level is low. Fill the fuel tank. Fill and bleed the fuel lines to the engine.