Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 3-28 Section 3 – Installation and Operation CFP83 Series Initial Start-Up (Cont) Check Initial Crankcase Oil Level: CAUTION Never operate the engine with the oil level below the low (“L”) mark or above the high (“H”) mark on the dipstick Check the oil level. NOTE : No change in oil viscosity or type is needed for new or newly rebuilt engines. If below the low mark, fill the crankcase to the low “L” (low) mark on the dipstick. See Lubricating Oil Recommendations and Specifications in Section 10 for oil specifications. See the Lubricating Oil System Specification for quantity that may be required. Pre-Lubricate the Turbocharger:

CAUTION New turbochargers must be pre-lubricated before startup. Failure to pre-lube the turbochargers will result in turbocharger bearing failure. Remove the turbocharger oil inlet line. Pre-lubricate the housing by adding 50 to 60 cc (2 to 3 oz.) of clean engine lubricating oil. Replace the line. Pre-Lubricate the Engine NOTE: Do not prime the engine lubricating system from the by-pass filter. On the top of the fuel pump, disconnect the electric fuel solenoid. Make sure that the fuel pump solenoid wire terminal does not touch the engine. Close the fuel shutoff valve from the fuel tank to prevent the engine from starting.

Prime the engine lubricating system until a 30 psi [207 kPa] minimum pressure is obtained. Drawing No. 9777, Section 3, Rev. 02-07