Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 3-30 Section 3 – Installation and Operation CFP83 Series Initial Start-Up (Cont) Drawing No. 9777, Section 3, Rev. 02-07 NOTE: No change in oil viscosity or type is needed for new or newly rebuilt engines. If below the high mark, fill the crankcase to the high “H” (high) mark on the dipstick. See Lubricating Oil Recommendations and Specifications in Section 10 for oil specifications. See the Lubricating Oil System Specification for quantity that may be required. Initial Test Run Move the throttle lever to mid-speed pos ition. Start the engine. Immediately move the throttle to the low idle position. Allow the engine to operate at low idle speed (700 RPM).

Check the lubricating oil pressure within 15 seconds after the engine starts. Operate the engine at set point for 8 to 10 minutes. Check for leaks, unusual noises, or other indications of incorrect operation. Shut off the engine and correct any problems found during the inspection before proceeding. After 8 to 10 minutes, stop the engine. Check the engine oil and expansion tank coolant levels. Top off if necessary. Clean the raw water strainer.