Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 3-32 Section 3 – Installation and Operation CFP83 Series Initial Start-Up (Cont) NOTE : Test button triggers overspeed at 10% below normal. Depress the “TEST” button push-button on the inside of the panel. Turn the screw to increase speed. Verify overspeed trip/indications. Operate the RESET switch on the front of the engine control panel. Repeat if necessary to further adjust the overspeed stop setting. Start the engine. Check operation at rated speed. Shut off the engine. Press the “AUTO” button so the fire pump will be ready to start automatically. Drawing No. 9777, Section 3, Rev. 02-07