Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 3-34 Section 3 – Installation and Operation CFP83 Series Initial Start NOTE : The object of this test is to check that the engine starts and operates normally with oil pressure being displayed and raw water flow being established to the coolant heat exchanger. Operation at the factory-adjusted rated speed is also checked. NOTE : If the engine does not start, vent the fuel system. Refer to Air in Fuel in Section 7, for instructions on how to vent the fuel system. FACTORY SETTING NOTE : If the engine still will not start, troubleshoot as per Engine Cranks But Will Not Start (No Exhaust Smoke) or Engine Difficult to Start or Will Not Start - Exhaust Smoke Present in Section 12.

ENGINE SPEED SETTING: (@ HP SETTING) OVERSPEED SWITCH SETTING: NOTE : When the engine starts, immediately check that oil pressure is displayed. It should be on-scale within a few seconds. Stop the engine if oil pressure is not displayed within about 15 seconds. NOTE : When the engine starts, immediately check that raw water flow is established through the coolant heat exchanger. Raw water flow should be established immediately but some delay may occur before the flow exits the heat exchanger drain connection. NOTE : Rated speed is displayed on the Factory Setting Tag described in Section 2. NOTE : If the engine fully loaded, it should operate at rated speed.

Unloaded, it may operate about 10% faster. If it becomes necessary to adjust the engine’s actual speed to match the rated value, refer to Rated Speed Setpoint Adjustment (CFP83-F10, F20, F30) or Rated Speed Setpoint Adjustment (CFP83-F40) in this section. Drawing No. 9777, Section 3, Rev. 02-07