Section 3 – Installation and Operation Page 3-35 CFP83 Series Initial Start (Cont) Start the engine using either the CRANK BATT A or the CRANK BATT B switch positions. Check that the engine starts and operates at about rated speed. NOTE : If oil pressure is not present or if the Low Oil Pressure Light does not go out, stop the engine and troubleshoot as per Lubricating Oil Pressure Low in Section 12. Check that lubricating oil pressure is displayed within 15 seconds after the engine starts. NOTE : Raw water should be flowing through the heat exchanger and water pressure shown on the local pressure gauge should be no more than 414 kPa (60 psig).

Check that raw water is flowing through the heat exchanger. Check that raw water supply pressure is correctly adjusted. Operate the engine for 8 to 10 minutes. Check for leaks, unusual noises, or other indications of incorrect operation. Shut off the engine by pressing the AUTO position on the AUTO/MANUAL rocker switch and by momentarily pressing the RESET switch. Check that raw water flow stops automatically shortly after the engine stops. Correct any problems found during the inspection before proceeding. Check the engine lubricating oil level. Refer to Check Lubricating Oil Level in Section 5. Top off if necessary. Check the coolant heat exchanger’s coolant level.

Refer to Check Coolant Level in Section 5. Top off if necessary. Check the raw water strainer. Clean the strainer if necessary. Drawing No. 9777, Section 3, Rev. 02-07