Section 3 – Installation and Operation Page 3-45 CFP83 Series Crank Terminate Adjustment and Testing NOTE : The crank terminate signal to the remote fire pump controller informs the controller that the engine has started. This allows the controller to terminate the selected crank signal to the engine. This crank terminate signal is produced by the overspeed switch in the engine’s local control panel. The setpoint for the crank terminate signal is adjusted at the factory to a value above normal idling speeds but less than the rated speed. The setpoint should not require adjustment unless it is necessary to test the switch operation or to replace the overspeed speed switch. NOTE :

If using this procedure for troubleshooting, perform the test portion prior to making any adjustments. Verify automatic reset of the crank terminate signal. Prepare Place the fire protection system in a safe mode for engine service. Place the AUTO/MANUAL rocker switch in the MANUAL position. REMOVE BATTERY POWER BEFORE SERVICING ENGINE OR CONTROLS For safety reasons, both batteries must be disconnected before performing service on the Firepump Engine or on any of its controls. Before disconnecting the batteries, place the Firepump Controller in its appropriate service position in order to avoid a “Battery Failure” alarm. Wear safety glasses when disconnecting batteries!

Next, disconnect both batteries at their terminals. Drawing No. 9777, Section 3, Rev. 02-07