Page 3-46 Section 3 – Installation and Operation CFP83 Series Crank Terminate Adjustment and Testing (Cont) Adjust NOTE : Refer to Drawing 10423 Sheet 1 in Section 13. Open the engine’s local control panel cover. Disconnect the GRAY/RED (MPU +) wire from PICK-UP terminal 1 at the speed switch. Disconnect the GRAY/BLK (MPU -) wire from PICK-UP terminal 1 at the speed switch. Connect a signal or pulse generator to the switch inputs with the same signal polarity. Adjust the pulse generator to about 1100 cycles or pulses per second. Remove the cover from the speed switch CRANK/TACH CAL potentiometers.

If, with this signal, the CRANK LED is illuminated on the speed switch, turn the CRANK potentiometer E5 clockwise until the LED extinguishes. Then, turn the CRANK potentiometer E5 slowly counterclockwise until the CRANK LED illuminates. Replace the cover on the speed switch. Remove the signal generator. Connect the GRAY/RED (MPU +) wire at PICK- UP terminal 1 at the speed switch. Connect the GRAY/BLK (MPU -) wire at PICK- UP terminal 1 at the speed switch. Drawing No. 9777, Section 3, Rev. 02-07