Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 3 – Installation and Operation Page 3-47 CFP83 Series Crank Terminate Adjustment and Testing (Cont) For safety reasons, both batteries must be re- connected before putting the engine and fire protection system controller back in service. Wear safety glasses when reconnecting batteries! Reconnect the batteries at their terminals after all service work has been completed. Test NOTE : Monitor fire pump controller operations from the controller. Check for the crank terminate signal at the input terminals and observe that the controller removes the crank output to the engine. Connect a digital voltmeter at crank terminate output of the local control panel between TB2 (+) and TB11 (-).

Refer to Drawing 10423 Sheet 1 in Section 13. NOTE : The engine’s rated speed is displayed on the Factory Setting Tag described in Section 2. Place the AUTO/MANUAL rocker switch in the AUTO position. Start the engine from the fire pump controller. Observe that the engine starts and accelerates to about rated speed. Observe that the CRANK terminal LED on the speed switch is illuminated. Check that the local digital voltmeter indicates the 12 VDC standard (24 VDC optional) signal output voltage. When testing is done, stop the engine. Remove the digital voltmeter. Close the cover on the engine control panel. Drawing No. 9777, Section 3, Rev. 02-07