Page 3-48 Section 3 – Installation and Operation CFP83 Series Isolated Acceptance Testing Demonstrate the manual local start, operation, and shutdown of the fire pump from the engine’s local starter- solenoid controls. Demonstrate that the engine will operate in the event of blown fuses or other faults in the local control panel. Demonstrate manual engine speed control. Manual raw water valve operations are required. Demonstrate the manual local start, operation, and shutdown of the fire pump from the engine’s control panel. Demonstrate that the engine starts, operates at speed, and stops in the event that the fire pump controller is not functioning.
Demonstrate the start of the fire pump engine using each battery set separately. Demonstrate that the fire pump engine alternator operates while the engine is running. Demonstrate that any customer supplied battery charging systems operate when the engine is not running. Integrated Acceptance Testing Demonstrate the start-up, operation, and shutdown of the fire pump engine in response to operations of the customer-installed fire pump controller. Perform this testing with the testing of the fire pump controller. Demonstrate that the fire pump controller provides design indications and/or alarms for simulated engine oil pressure, water temperature, and overspeed faults.
Demonstrate the actual operation of the crank terminate output from the overspeed switch. Participate in any flushing, pressure testing, flow testing, or capacity testing required for the fire protection system. Complete the Cummins Fire Power Start-Up Inspection (SUI) Checklist. This is available on the Cummins Fire Power web site (www.cumminsfirepower.com/startup). When these items have been demonstrated, contact operating personnel responsible for fire protection system that engine is ready for service. Drawing No. 9777, Section 3, Rev. 02-07