Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 3 – Installation and Operation Page 3-49 CFP83 Series General Operating Information Cummins fire pumps are tested before being shipped from the factory and are ready to put to work in application regarding to fire emergencies. Correct care of your engine will result in longer life, better performance, and more economical operation. Follow the daily maintenance checks listed in Maintenance Guidelines, Section 4. Check the water temperature and oil pressure indicators, warning lights, and other gauges daily to make sure they are operational.

Normal Remote Starting Procedure The fire pump engine starts automatically upon receipt of the start command from the customer installed fire control panel. The remote command starts the engine when the AUTO/MANUAL rocker switch at the local; control panel is in the AUTO position. The remote start command consists of either the Crank A or the Crank B signal. Only one should be selected. The engine continues to operate as long as the run signal is present. When the run signal is lost, the engine promptly stops. When the engine starts, the crank terminate signal is sent to the fire control panel to indicate that the engine is running.

How this is displayed depends upon the fire control panel manufacturer. This indication should be checked in the event that an automatic start is initiated. If the signal is not present, the engine can be started locally by using the Emergency Starting Procedure in this section. The engine may be stopped locally by selecting the manual position on the AUTO/MANUAL rocker switch and by pressing the local RESET switch. Drawing No. 9777, Section 3, Rev. 02-07