Page 3-50 Section 3 – Installation and Operation CFP83 Series Normal Local Starting Procedure Overview The fire pump engine is started locally for testing and maintenance. Local starts for testing will be performed at rated speed. That is, the engine starts and promptly ramps up to operating speed. If it is necessary to operate the engine at idle speed for maintenance or troubleshooting, the engine speed must be manually reduced. After maintenance or troubleshooting, the speed must be manually reset to the rated value shown on the Factory Setting Tag in see Section 2.

Local Starting Procedure for Testing CAUTION To prevent damage to the starter, do not engage the starting motor more than 15 seconds. Wait 15 seconds between each attempt to start (electrical starting motors only). Start the Engine Press the MANUAL position on the AUTO/MANUAL rocker switch. Observe the battery voltages displayed on the engine control panel. Use the battery with the highest indicated voltage. NOTE : Depress the selected switch for up to 15 seconds or until the engine starts. Repeat up to three times if necessary. Start the engine using either the CRANK BATT A or the CRANK BATT B rocker switch positions. NOTE :

If the engine does not start after three attempts, check the fuel supply system. Absence of blue or white exhaust smoke during cranking indicates no fuel is being delivered. Engine oil pressure must be indicated on the gauge within 15 seconds after starting. Stop the Engine To stop the engine, select the AUTO position on the AUTO/MANUAL rocker switch and press the RESET switch. Drawing No. 9777, Section 3, Rev. 02-07