Section 3 – Installation and Operation Page 3-51 CFP83 Series Normal Local Starting Procedure (Cont) Local Starting Procedure for Maintenance or Troubleshooting Engines used in fire pumps or standby service are expected to transition from crank to full load within a short period of time. CAUTION Do not idle the engine for excessively long periods. Long periods of idling (more than 10 minutes) can damage an engine because combustion chamber temperatures drop so low the fuel will not burn completely. This will cause carbon to clog the injector spray holes and piston rings, and can cause the valves to stick.
If the engine coolant temperature becomes too low (60°C [140°F]), raw fuel will wash the lubricating oil off the cylinder walls and dilute the crankcase oil; therefore, all moving parts of the engine will not receive the correct amount of lubrication. Adjust the fuel pump as per instructions in Section 7 to get idle speed. Manually position the fuel pump at mid throttle position. Press the MANUAL position on the AUTO/MANUAL rocker switch. CAUTION To prevent damage to the starter, do not engage the starting motor more than 15 seconds. Wait 15 seconds between each attempt to start (electrical starting motors only).
Start the engine using either the CRANK BATT A or the CRANK BATT B switch positions. NOTE : If the engine does not start after three attempts, check the fuel supply system. Absence of blue or white exhaust smoke during cranking indicates no fuel is being delivered. Engine oil pressure must be indicated on the gauge within 15 seconds after starting. Drawing No. 9777, Section 3, Rev. 02-07