Section 3 – Installation and Operation Page 3-53 CFP83 Series Jumpering the Batteries NOTE : If a battery charging system is not provided, the engine can be started using known good batteries to provide a temporary power source. Once the engine is started, disconnect the added batteries and allow the engine’s alternator to charge the existing batteries. It may take some time to charge the batteries with this method. NOTE : For maintainable lead acid batteries as supplied by Cummins N Power, check the state of charge by the measurement of battery cell specific gravity. Refer to Battery Testing in Section 7 for more information. WARNING Batteries can emit explosive gases.
To avoid personal injury, always ventilate the compartment before servicing the batteries. To avoid arcing, remove the negative (-) battery cable first and attach the negative (-) battery cable last. CAUTION When using jumper cables to start the engine, make sure to connect the cables in parallel: Positive (+) to positive (+) and ground (-) to ground (-). The accompanying illustration shows a typical parallel battery connection. This arrangement, positive (+) to positive (+), doubles the cranking amperage. Use this type of connection to jump start the engine. For a 24 VDC system, two or more 12 VDC batteries are connected in the parallel connection as shown.
If jumpering a 24 VDC battery setup, another 24 VDC battery pair is required as the source. The accompanying illustration shows a typical series battery connection. This arrangement, positive (+) to negative (-), doubles the voltage. Do not use this type of connection to jump start the engine using a second 12 VDC battery. Drawing No. 9777, Section 3, Rev. 02-07