Section 3 – Installation and Operation Page 3-55 CFP83 Series Emergency Manual Starting Procedures Overview The engine starts automatically in the event of a fire emergency. However, if it fails to start automatically, the engine can be started locally by either of two means. The Normal Local Starting Procedure in this section can be used to start the engine if it fails to start because of a failure in the remote fire control system. Operating the engine with this procedure will automatically control raw water flow. Additionally, manual means are available to start the engine in the event of some local failures.
This procedure requires the manual operation of the raw water valves and the use of the manual starting lever on either of the two starting solenoids. Use the following procedures as specified: If the red low lube oil pressure light is illuminated, attempt an Emergency Manual Mode Electrical Start. If the red low lube oil pressure light is not illuminated, attempt an Emergency Manual Mode Non-Electrical Start. Also, if the fuel shutoff valve is known to be faulted, attempt an Emergency Manual Mode Non-Electrical Start. Drawing No. 9777, Section 3, Rev. 02-07