Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 3 – Installation and Operation Page 3-59 CFP83 Series In the event the automatic start is not operational, pull on the throttle handle assembly which will move the lever to the run position to start the engine. Run Turn handle assembly to lock throttle cable assembly in position to allow the engine to run in manual mode. Press down on the crank solenoid lever to engage the starter while in manual mode. Depress until engine starts. NOTE : If first crank solenoid lever does not engage the starter, repeat on second crank solenoid lever. Drawing No. 9777, Section 3, Rev. 02-07 Close d