Komatsu — WHEN REQUIRED

. MAINTENANCE MAINTENANCE PROCEDURE CHECK AND MAINTENANCE AIR CONDITIONER Check Level of Refrigerant (gas) WARNING Inspection and Maintenance Items 4 - 35 (Only for m achines equipped with an air If the refriger ant used in the air c onditioner ge ts into your eyes o r on your hands, it may cause loss of sight or frostbite. Do not touch the ref rigerant. Never loo sen any part o f the refrigerant ci rcuit. as is leaking. Do not bring any flame close to any point whe re the refrigerant g as is leaking. If the level of the refrigerant (gas) is low, the cooling effec t will be reduced.

R un the engine at high idle, a nd check the flo w of the refrigerant gas (R134a) in th e refrigeran t circuit through t he sight glass (2) (in spection window) of the recei ver (1) when the cooler is running at h igh speed. (A) No bub bles in refrigerant flow: Suitab (B) Some b ubbles in flow (bu bbles pass Lack of refr (C) Colorles s, transparent: N o refrigeran REMARK When there are bubbles, the refrigerant g as level is low, so contact your Koma tsu distributors t o have refri gerant added. If the air conditioner is run with the r efrigerant gas level low, it will cause damage to the compressor.

Inspection During Off Season Even during the off-season, operate the a ir conditioner for 3 to 5 minutes once a month to m aintain the oil film at al parts of the compressor.

Check, maintenance items Guidelin Content of check, maintenance e for maintenance interval Refrigerant (gas) Charge amount Twice a ye ar (spring, autumn) Air conditioner condenser Clogged fins Every 500 hours Compressor Operating condition Every 400 0 hours V-belt Damage, tension Every 250 hours Blower motor, fan Operating condition When requ (does it make abnormal noise?) ired Control mechanism Operating condition (does it function normally?) When requ ired Piping mounts Mounting condition, looseness at tightening or When req connecting portions, leakage of gas, damage uired