Batteries 54.03 Battery Charging CAUTION Use a reliable, automatic, temperature-sensing, voltage-regulated charger to charge gel cells. Any other type of charger will damage the gel cell. 4. Connect the charger leads directly to the battery following the charger manufacturer’s instructions. Rock the charger lead clamps to make sure there is a good connection. 5. Turn on the charger and set the charging rate between 13.8 and 14.1 volts (2.30 to 2.35 volts per cell). CAUTION To prevent damage, do not open a sealed gel cell or charge it in excess of 14.1 volts (2.35 volts per cell). 6. After about one minute, check the initial charge current.
To charge to 90 percent of full charge, see Table 5 to determine the approximate time of completion. To charge to 100 percent of full charge, see Table 6 to determine the approxi- mate time of completion. IMPORTANT: If the battery feels hotter than 125°F (52°C) or if rapid gassing occurs, stop charging the battery and allow it to cool. 7. When finished, turn the charger off. WARNING Always turn the charger off before disconnecting it. Touching a charger lead when the circuit is live could create a spark and cause an explosion, resulting in personal injury. 8. Disconnect the charger cables from the battery. Business Class M2 Workshop Manual, Supplement 10, September 2006 150/4