PTO and Pump Electrical Controls 54.38 Troubleshooting PTO and Fire Pump Control Switch and Interlocks Test Test No. Test Procedure Test Result Action 2 Are any of the five SSn ID#s equal to 0? Yes Go to test no. 5. No Go to test no. 3. 3 In ServiceLink, open the "Switch Expansion Module 1, Smart Switches" Datalink Monitor template. Go to test no. 6. Look at each of the six SEM to BHM outputs: SS1 ID#, SS2 ID#, SS3 ID#, SS4 ID#, SS5 ID#, and SS6 ID#. Yes If diagnosing the PTO, are any of the five SSn ID#s equal to 38? Go to test no. 4. No If diagnosing the fire pump controls, are any of the five SSn ID#s. equal to 104? 4 Are any of the six SSn ID#s. equal to 0? Yes Go to test no. 5.
Repeat test no. 3 using the next SEM template. For example, "Switch Expansion Module 2, Smart Switches." No 5 Is fault code 164 s022 07 active? Check the following and make the necessary repairs: Check if PTO or PUMP smart switch is installed and connected. Yes Check smart switch wir- ing. Check the smart switch. If the smart switch is in- stalled in SEM, check SEM. The PTO or fire pump controls smart switch is not programmed for the vehicle. Check and apply the proper 26-01032-xxx refer- ence parameter.
No 6 Toggle the PTO smart switch on and off several times while observing the Datalink Monitor template which shows SSn ID# equal to 38 for PTO diagnosis, or 104 for fire pump controls diagnosis. Yes Go to test no. 7. Check the following and make necessary repairs: If using the Smart Switches template, look for a change under the "BHM Inputs" heading in the input voltage for the smart switch. Check smart switch wir- ing. If using one of the Switch Expansion Modules templates under "SEM to BHM" heading, look for a change in the state of the "SSn Pos" annunciator for the smart switch. No Check the smart switch. If the smart switch is in- stalled in SEM, check SEM.
Is there a change in voltage or state when toggling the PTO switch? Business Class M2 Workshop Manual, Supplement 22, September 2012 300/6