Cab Heater and Air Conditioner, Valeo 83.00 Refrigerant Service Operations 6. Measure the oil recovered during the recovery process. The refrigerant system will have to be filled with the same quantity of new refrigerant oil. If the system is contaminated with moisture, all of the compressor oil must be replaced with clean oil. If the system is heavily contaminated with desiccant or grit, replace the compressor, expansion valve, and receiver-drier, and flush the condenser and evaporator(s). After the system is charged, perform a performance check to ensure that the heat exchangers are not plugged. 1 2 f830489b 11/14/95 Evacuating 1. Vapor 2. Water Fig.

1, Water to Vapor The main purpose in evacuating the refrigerant sys- tem is to remove noncondensable gases (NCG), such as nitrogen and air. The secondary purpose is to boil off free water molecules. Measuring Vacuum Vacuum should be measured with an electronic ther- mistor vacuum gauge, which is designed for use with high vacuum pumps and can accurately read as low as 100 microns. This gauge can have an analog scale or a digital (LED or LCD) display. Water in the refrigerant can form ice crystals at the expansion valve. The ice crystals retard or stop the flow of refrigerant, causing a reduction or complete stoppage of cooling.

As the expansion valve warms due to the lack of refrigerant, the ice melts and passes through the expansion valve. Then refrigerant will flow again, until the ice crystals re-form. The re- sult is intermittent cooling. The location of the vacuum gauge will affect the reading. The closer to the vacuum source, the lower the reading will be. Follow the manufacturer’s instruc- tions for proper use of the vacuum gauge. Refrigerant oil has an extremely high moisture ab- sorption capacity. Normally, the moisture picked up by the oil is passed off to the receiver-drier.

If exces- sive moisture exists in the system, the lubricating ability of the oil is reduced, which could damage the compressor and other components. Effects of Pressure on the Boiling Point of Water If the pressure will not stabilize, suspect a leak. If it does stabilize at a vacuum that is too high, for ex- ample 1500 microns Hg, it is an indication of mois- ture and more evacuation is required. Holding a vacuum only means that there is no leak present under a vacuum. Other leaks may exist when the system is pressurized, so a proper leak test must be performed in conjunction with holding a vacuum.

Maintaining an Oil-Lubricated Vacuum Pump Water boils at 212°F (100°C) at an atmospheric pres- sure of 14.7 psi (101 kPa), at sea level. At higher elevations the atmospheric pressure is lower, which allows water to boil at lower temperatures. See Table 1 for boiling temperatures of water at con- verted pressures. Maintenance is important for a high-vacuum pump. The oil must be changed at regular intervals to pre- vent moisture buildup, which will cause decreased pump performance and eventual pump failure. Another way to boil and remove water from the air conditioning system, is by lowering the system pres- sure to a vacuum, to cause the moisture to vaporize at normal ambient temperatures.

A vacuum pump can reduce the pressure in the system. Since the pressure is lowest at the pump, NCG and water vapor are pulled out of the system. This process is called evacuation or dehydration. See Fig. 1 . Pumping down for extremely wet air conditioning sys- tems can completely saturate the pump oil, which will require the replacement of the vacuum pump oil. Business Class M2 Workshop Manual, Supplement 20, September 2011 220/2