PowerFlow Fire Pump 90.01 Troubleshooting Problem—Relief Valve Does Not Relieve When Valves are Closed Possible Cause Remedy Problem—Relief Valve Does Not Relieve When Valves are Closed Incorrect pilot valve setting. Repeat the proper procedure for setting the relief valve. Pilot valve inoperative. Disassemble, clean, and lubricate. Inspect the control valve diaphragm for wear or damage. Relief valve inoperative. Disassemble, clean, and lubricate. Problem—Relief Valve Does Not Recover When Valves are Opened Possible Cause Remedy Problem—Relief Valve Does Not Recover When Valves are Opened Dirt in system resulting in slow or sticky operation. Disassemble, clean, and lubricate.

Problem—Unable to Attain Proper Setting Problem—Unable to Attain Proper Setting Incorrect procedure. Check procedure and reset. Possible Cause Remedy Blocked strainer. Disconnect the pilot valve supply line from the discharge side of pump. Remove the 90-degree fitting where the supply line connects to the pump. The strainer is attached to this fitting. Clean or replace the strainer and fitting assembly. Dirt in pilot valve. Disassemble, clean, and lubricate. Hunting condition. Insufficient water supply to the pilot valve. Check strainer and supply lines. If there is dirt in the pilot valve, disassemble, clean, and lubricate.

Problem—TPM Valve Does Not Relieve Problem—TPM Valve Does Not Relieve Sensing valve inoperative. Disassemble, clean, and lubricate. Inspect the control valve diaphragm for wear or damage. Possible Cause Remedy PG relief valve inoperative. Disassemble, clean, and lubricate. PG relief valve sluggish. Check and clean the discharge and suction strainers in the pump body. Business Class M2 Workshop Manual, Supplement 8, September 2005 300/4