PowerFlow Fire Pump 90.01 Troubleshooting Problem—Mechanical Seal Leaks Problem—Mechanical Seal Leaks Leak at mechanical seal. If the mechanical seal is leaking it will have to be replaced. If properly cared for, the mechanical seal should be almost maintenance free. Water quality will greatly affect seal life. Possible Cause Remedy The most common failure of the mechanical seal is from thermal-shock (running the pump dry, heating up the seal, then opening to a cool or cold water supply); the seal may shatter. Problem—Pump Gear Box Does Not Function Properly Problem—Pump Gear Box Does Not Function Properly Possible Cause Remedy Water in gear box. Locate and repair the leak.
Remove and clean the gear box filter. Replace the transmission oil. Water leaking onto the input drive shaft of the pump gear box will actually be screwed into the pump transmission past the oil seals. This is not a seal problem. Be certain the slinger(s) are in place. Check the pump gear box cooling line for internal fractures. Pump gear box will fill with water and overflow through breather. Whine in gear box. Check the oil level. If oil is low, helical gears and/or tapered bearings will whine. Check oil pressure. If the filter is clogged, oil pressure will be low. Drain oil and check for metal. Remove filter and check for metal.
If metal is detected, pump gear box will have to be disassembled for complete inspection and repairs. Knock or rattle in gear box. Check for gears missing teeth. Check for damaged bearings. Disassemble and repair. * * The cause may include foreign objects, low or contaminated oil, or low oil pressure. Low oil level or pressure will result in the transmission being damaged due to overheating. Dry Vacuum Test 4. The vacuum should not drop more than 10 inHg (33.9 kPa) in 5 minutes. Do not operate the pump priming device once the 5-minute test has begun. 1. Open all the intake valves. 2. Cap all intakes, and close and uncap all dis- charge valves. 3.
Using the pump’s priming devices, develop a vacuum of at least 22 inHg (74.5 kPa) for 30 seconds for pumps up to 1250 gpm, or 45 sec- onds for pumps 1500 gpm or greater. NOTE: Reduce the maximum vacuum attained by 1 inHg (3.4 kPa) for each 1000 ft (305 m) of elevation of the test site above 2000 ft (610 m). Business Class M2 Workshop Manual, Supplement 8, September 2005 300/5