Deutz — 8.2 EMR

SERDIA WHAT SHOULD YOU DO IF...? BASIC INFORMATION ON MAKING CORRECTIONS TO SETTINGS: Corrections to settings should be made with the engine running. Increase of P-I-D parts results in broader speed control fluctuation range. Enter the value you wish to correct in the field "new value". One possible method is as follows: mark the old value with the mouse and type in the new value (this automatically removes the old value). Click on the switch "PC->ECU" in order to send the new value to the ECU. The governor takes over the new governor characteristics; you will recognise the result by the engine's running characteristics.

After you have successfully made the required corrections to the settings and before you disconnect the power supply (Chapter 15), you must save the new parameter setting in the EMR. To do so, click on the switch "Save in ECU". BASIC GOVERNOR SETTING: The ECU at end of line is programmed with the following standard values: 1 Differing standard values are possible, depending on the engine type and the application! Standard values, speed and load-dependent parameters (page 17): 3 performance maps for P, I, und D part = fct (speed, fuel injection volume). 20-46 Parameter (Variable) Standard values Remarks Genset Vehicle SpeedGvnr: P part SpeedGvnr: 1 part SpeedGvnr:

D part 18-201 10,0 5-12 4,0 10,0 2.5 Basic setting gain factors P-I-D parts. These parameters are in- dependent of the engine status (speed, continuous load active). They are the main instruments used when setting the governor. SpeedGvnr: damping 90,0 65,0 Reduction of the governor parameters for the static range. SpeedGvnr: damping range 15,0 80,0 Speed band around setpoint value. Within this speed band the en- gine runs under steady-state conditions accurately and smoothly without reacting violently to speed variations. PosGvnr: P part PosGvnr: I part PosGvnr: D part PosGvnr: DT2 part PosGvnr: gain PosGvnr:

gain range 10,0 10-151 5-101 8,0 160-180 0,25 10,0 5,0 5,0 8.0 180.0 0,25 Corrections to settings should only be made following approval of head office. Parameters (Variable) Standard value Remarks X: Engine speed position values (1/min) 600 ... 2500 7 speed values Y: Quantity position values (cmm/Hub) 0, 20...100 4 injection volume values Map (%) 100 Total of 3 x 28 entries. The entry "100%" results in assumption of the governor P-I-D parts (page 4). Corrections must be made at the relevant working point.