Caterpillar — MAINTENANCE INTERVAL SCHEDULE (STANDBY GENERATOR SET ENGINES)

141 Maintenance Section Water Pump - Inspect 4. After exercising the generator set, stop the engine according to this Operation and Maintenance Manual, “Engine Stopping” topic (Operation of the zinc rods and the number of zinc rods that are installed. Section). 5. Perform the procedures that are described in this Operation and Maintenance Manual, “After Stopping Engine” topic (Operation Section). 6. Ensure that the control switches are in the correct position for automatic starting of the generator set. For the location of the zinc rods, see the literature that is provided by the OEM of the installation. Inspect the Zinc Rods 1.

Remove 100524084 Water Pump - Inspect SMCS The engineer for the operation must determine the interval for inspecting the zinc rods. The interval for inspecting the zinc rods will depend on the size Code: the zinc rod. 2. Inspect the zinc rod. Ensure that the zinc rod will remain effective until the next scheduled inspection. 1361-040 A failed water pump might cause severe engine a. If the zinc rod has deteriorated excessively, install a new zinc rod. overheating problems that could result in cracks in the cylinder head, a piston seizure or other potential damage to the engine. Visually inspect the water pump for leaks.

If leaking of the water pump Seals is observed, replace all of the water pump seals. Refer to the Service Manual for the disassembly and assembly procedure. Inspect the water pump for wear, cracks, pin holes and proper operation. Refer to the Service Manual or consult your Caterpillar dealer if repair is needed or replacement is needed. 100940056 Zinc Rods - Inspect/Replace SMCS Code: 1388-040; 1388-510 Corrosion in sea water circuits can result in premature deterioration of cooling system components, leaks, and possible cooling system contamination. The corrosion may be caused by the lack of zinc rods in the sea water system.

Zinc rods are installed in the sea water cooling system of the engine in order to help prevent the corrosive oxidation that is caused by sea water. Electrical current is conducted through the contact of the zinc rods with the cooling system components. The zinc rods oxidize rather than the cooling system components. Rapid deterioration of zinc rods may indicate the presence of uncontrolled electrical currents from improperly installed electrical attachments or improperly grounded electrical attachments. g00481100 Illustration 92 b. Tap the zinc rod lightly with a hammer. zinc rod breaks, If the install a new zinc rod. 3.

If the zinc rod will be reused, scrape the layer of oxidation from the zinc rod before installation. The layer of oxidation reduces the effectiveness of the zinc rod. Replace the Zinc Rods 1. Use pliers to unscrew the old zinc rod from the plug. if not enough material remains or the zinc rod has broken off, drill the zinc from the plug. 2. Clean the plug.