40 Operation Section Engine Features and Controls The ECM will automatically perform the following functions when high aftercooler coolant temperature 100823448 occurs: Alarms and e Warning SMCS 7400 e Derating This section contains some general information about the function of typical engine protective devices. e Shut down The default settings that are programmed Code: Shutoffs Alarms and shutoffs are electronically controlled. at the The operation of all alarms and shutoffs utilize factory are listed in Table 16. components which are actuated by a sensing unit.
The alarms and shutoffs are set at critical operating temperatures, pressures, or speeds in order to protect the engine from damage. Table 16 Aftercooler Coolant Temperature Parameter Default Setting Generator set warning 102 °C (215 °F) The alarms function in order to warn the operator when an abnormal operating condition occurs. The 50 °C (122 °F) when a more critical abnormal operating condition occurs. The shutoffs help to prevent damage to the equipment.
setpoint shutoffs function in order to shut down the engine Marine auxiliary warning setpoint Warning delay 5 seconds Derate setpoint 107 °C (225 °F) Derate delay 5 seconds Maximum time of derating 480 seconds Hysteresis 3 °C (5.4 °F) Security level Password required Maximum derating 25% Shutdown setpoint 107 °C (225 °F) Shutdown delay | 5 seconds If the aftercooler coolant temperature is above 102 °C (215 °F) for five seconds, a warning will occur. To deactivate the warning, the aftercooler coolant temperature must be below 99 °C (210 °F). If an engine protective device shuts off the engine, always determine the cause of the shutoff.
Make the necessary repairs before attempting to start the engine. Become familiar with the following information: e Types of the alarm and shutoff controls e Locations of the alarm and shutoff controls | e Conditions which cause each control to function e Resetting procedure that is required before starting the engine For information about the specific alarms and shutoffs for the engine, see this Operation and If the aftercooler coolant temperature is above 107 °C (225 °F) for five seconds, a derating will Maintenance Manual, (Operation Section). occur. The continuous schedule of the derating will reach 25 percent in 480 seconds.
When the aftercooler coolant temperature is less than 104 °C (220 °F), the percent of the derating is decreased until full power is restored. However, if the aftercooler coolant temperature rises above the setpoint again, the derating resumes. If the aftercooler coolant temperature is above 107 °C (225 °F) for five seconds, a shutdown will occur, “Monitoring System” topic 101099280 Control Panel SMCS 7451 Code: This section describes the Caterpillar Electronic Modular Control Panel Il+ (EMCP II+). For more detailed information, see Service Manual, RENR1200, “Electronic Modular Control Panel II+ (EMCP II+) for EU] Engines”.
If your generator set is equipped with a different control panel, refer to the literature that is provided for the panel or the generator.