45 Operation Section Engine Features and Controls e If the wire from terminal 6 to terminal 9 is not \ JOE BOO FISH” Se POLL “IRD UF Deoowh: installed on the engine control switch, the GSC+ does not power up when the switch is in the “OFF/RESET” position. Any active shutdown condition must be corrected before the service mode can be activated. e@ The engine control switch is in the “AUTO” position. After the service mode is activated, the keypad can be used for the options that are listed in Table 17. LELE ELE.
OT Table 17 Options of the Keypad g00579657 Illustration 36 Option Functions of the keypad during the service mode (1) “SCROLL RIGHT’ (2) “SCROLL UP” (3) “SCROLL DOWN” (4) “SELECT” (5) “ENTER” (6) “EXIT” (7) “SERVICE MODE” “SCROLL RIGHT” key (1) — This key is used for viewing of information and for scrolling of information. This key represents the number the password is entered. 1 when “SCROLL UP” key (2) — This key is used for scrolling up through information and for increasing the value of the information. This key represents the number During Service Mode Description OP1 View the fault codes. OP2-0 (1) View the setpoints for the engine and/or the generator.
OP2-1 “) View the setpoints of the protective relays. OP2-2 (1) View the setpoints for the calibration that was programmed at the factory. OP3 (1) Enter the password. OP4 @) Clear the fault codes. OP5-0 @) Program the engine and/or the generator. OP5-1 Program the protective relays. @) OP6 @ Program the spare inputs and outputs. OP7 2) Program the hour meter. OP8 @ Program the voltmeter and/or the ammeter. decreasing the value of the information. This key OP9 @ Verify the setpoints for the engine. represents the number entered. OP10 @ Adjust the offset of the AC. 2 when the password is entered.
“SCROLL DOWN” key (3) — This key is used for scrolling down through information and 3 when for the password is “SELECT” key (4) — This key is used to select the information for viewing or for changing. This key is also used for starting and stopping of scrolling. “ENTER?” key (5) — This key is used to enter information into the memory of the GSC+. “EXIT” key (6) ~ This key only functions when the GSC+ is in the service mode. Press this key in order to exit the service mode. “SERVICE MODE” key (7) — Press this key in order to activate the service mode. The upper display will flash “SERV”, The service mode cannot be activated under the following conditions: e A shutdown condition is active.
To temporarily deactivate a shutdown condition, turn the engine control switch to the “OFF/RESET” position. | () A password is NOT required. (2) A password IS required. (3) This option is not available for EUI systems. For a complete description of the service mode, see Service Manual, RENR1200, “Electronic Modular Control Panel Il+ (EMCP Il+) for EUI Engines”.