Caterpillar — ENGINE FEATURES AND CONTROLS

46 Operation Section Engine Features and Controls Control Panel (Operation) “STOP/RESET” Hz indicators if any events have occurred. If the engine \/ oo — When the switch is turned to this position (12 o’clock), power is removed from the control panel! unless a jumper wire is installed between terminal 6 and terminal 9 of the engine control switch. This position will also reset the fault is operating, the engine is immediately shut off. This position is not recommended for normal engine shutoff. Ostany EMERGENCY STOP “STARTING AID” switch (3) — This optional switch can be used to manually inject ether during start-up. The switch is normally in the “OFF” position.

The “AUT” position allows the ECM to g00578489 Illustration 37 is described in this Operation and Maintenance (1) Speed potentiometer (option) (2) Engine control switch (3) “STARTING AID” switch (option) (4) Voltage adjust rheostat (5) “EMERGENCY STOP” button (6) “PANEL LIGHTS” switch Manual, “Programmable System (Operation Section). is used to control the engine rpm and the frequency of the generator. Engine control switch (2) — This switch is used to control the engine operation. The switch has four positions: “COOLDOWN/STOP”, “AUTO”, Parameters” topic Voltage adjust rheostat (4) — The rheostat is used to adjust generator voltage to the desired level.

Speed potentiometer (1) — The potentiometer these automatically control the ether injection. When the operator holds the switch in the “MAN” position, ether is injected according to the strategy that "MAN. START”, and “STOP/RESET”, This control is used instead of the rheostat that is located on the voltage regulator of the generator. “EMERGENCY STOP” button (5) — This button is used to stop the engine quickly in an emergency situation. When this button is pressed, the fuel injection is disabled and the air shutoffs (if equipped) are activated.

“AUTO” — This position (3 o’clock) enables the operator to control the engine from a remote location “PANEL LIGHTS” switch (6) — This switch turns the panel lights on and off. via a Customer Communication Module. The engine will start when the remote start/stop initiate contact Alarm is closed. The engine will shut down after the remote start/stop initiate contact opens. However, if the cooldown feature is programmed the engine will operate for the cooldown period before stopping. An alarm condition will not shut down the engine. However, an alarm may precede a shutdown. An alarm indicates a serious condition that requires “MAN.

START” — When the switch is turned to this position (6 o'clock), the engine will start. The engine will continue to run until the GSC+ receives a shut down signal. “COOLDOWN/STOP” — This position (9 o’clock) is used for manual stopping. If the cooldown feature is programmed, the engine will operate for a cool down period when the switch is turned to this position. After the cooldown, the fuel injection is terminated in order to stop the engine. If the cooldown feature is not programmed, the engine will stop immediately. The power to the control panel is maintained when the switch is in this position. The cooldown can be programmed from 0 to 30 minutes. The default cooldown is 5 minutes.

Module immediate attention. If an alarm condition occurs, the alarm module uses an indicator and a horn in order to inform the operator. Alarm modules are optional. There are several different types of alarm modules. The features of an alarm module are identified in Illustration 38.