Cummins — 3666003

Fuel Lift Pump C Series Page 5-40 Section 5 - Fuel System - Group 05 Look for a plugged supply tank vent first. Fuel prefilters, inline and water separator type, can become clogged and cause a loss of fuel flow. Check the prefilter for clogs or restrictions. In cold weather, check the prefilter for gelled fuel. Clean or replace the prefilter, if necessary. Check for kinks or bends in the fuel supply line that can cause a restriction in the fuel flow. Remove and blow out the fuel supply lines. Preparatory Steps WARNING Wear appropriate eye and face protection when using compressed air. Flying debris and dirt can cause personal injury.

Clean debris from the fuel line fittings and the fuel lift pump. Disconnect the low-pressure fuel lines. Refer to Procedure 006-024.